風管寬度超過1.2米時,應(yīng)當在管道下方安裝噴淋,采用下噴的形式,噴頭應(yīng)當設(shè)置在管道的下方,而不應(yīng)與管道齊平或者設(shè)置在管道上方或側(cè)方。噴淋頭間距不能小于15公分,注意放水時不能打開通風。采用早期抑制快速響應(yīng)噴頭和特殊應(yīng)用噴頭的場所,當障礙物寬度大于0.6m時,其下方應(yīng)增設(shè)噴頭。
When the width of the air duct exceeds 1.2 meters, a sprinkler should be installed below the duct, using a downward spray form. The sprinkler should be placed below the duct, not flush with the duct or above or on the side of the duct. The distance between sprinkler heads should not be less than 15 centimeters, and attention should be paid to not opening ventilation when draining water. In places where early suppression rapid response nozzles and special application nozzles are used, nozzles should be added below obstacles with a width greater than 0.6m.
消防噴淋系統(tǒng)噴頭安裝基本要求
Basic requirements for installation of fire sprinkler system nozzles
1、直立型噴頭安裝距樓板頂部距離為規(guī)范要求為75mm-150mm。
1. The installation distance of the upright nozzle from the top of the floor slab is required by the specifications to be 75mm-150mm.
2、有吊頂?shù)南麓剐蛧婎^安裝噴頭根部應(yīng)與吊頂平齊,為避免定位不準,可在吊頂龍骨標高確定后再安裝下噴支管;下噴頭與三通之間的短管長度不宜超過150mm。
2. The installation of hanging nozzles with suspended ceilings should be flush with the base of the nozzle. To avoid inaccurate positioning, the lower spray pipe can be installed after the elevation of the ceiling keel is determined; The length of the short pipe between the nozzle and the tee should not exceed 150mm.
3、邊墻型噴頭安裝離墻距離為50-100mm。
3. The installation distance of the side wall type nozzle from the wall is 50-100mm.
4、無吊頂時設(shè)置上噴頭;有吊頂時設(shè)置下噴頭,當?shù)蹴斏戏綈烅數(shù)膬艨崭叨瘸^800mm,且其內(nèi)部有可燃物時,要求設(shè)置上噴頭;噴頭在系統(tǒng)沖洗試壓合格后安裝;當噴淋支管高度大于1000mm時,應(yīng)設(shè)橫向加強支架;當不確定裝修方案是否有吊頂時可預(yù)留三通口,絲堵封堵。
4. Install upper nozzles when there is no ceiling; When there is a suspended ceiling, a lower nozzle should be installed. When the clearance height above the suspended ceiling exceeds 800mm and there are combustibles inside, an upper nozzle should be installed; The nozzle shall be installed after the system flushing and pressure test is qualified; When the height of the spray branch pipe is greater than 1000mm, a transverse reinforcement bracket should be installed; When it is uncertain whether the decoration plan has a suspended ceiling, a three-way port can be reserved and sealed with a screw plug.
5、噴淋管道末端應(yīng)采用梯形防晃支架;末端支架與噴頭之間的距離為400mm
5. The end of the sprinkler pipe should be equipped with a trapezoidal anti sway bracket; The distance between the end bracket and the nozzle is 400mm
6、當梁、通風管道、排管、橋架寬度大于1.2m時,增設(shè)的噴頭應(yīng)安裝在其腹面以下部位;風管下噴頭吊架應(yīng)采取管道延長風管另外一端邊緣,并在延伸管道末端設(shè)置吊架。
6. When the width of beams, ventilation ducts, ducts, and cable trays is greater than 1.2m, additional nozzles should be installed below their belly surface; The nozzle hanger under the air duct should be extended to the edge of the other end of the air duct, and a hanger should be installed at the end of the extended pipe.
7、噴淋管道安裝應(yīng)主管在下;噴淋管支管在主管上方,朝主管方向形成坡度,便于系統(tǒng)維護泄水。
7. The installation of sprinkler pipes should be supervised by the supervisor; The spray pipe branch is located above the main pipe, forming a slope towards the main pipe direction for easy maintenance and drainage of the system.